s 

 

3196 POWER QUALITY ANALYZER

Monitor and record the quality of power to analyze the cause of trouble when it occurs !


• Measure power factor
• Sags
• Swells
• Flicker
• Transients
• Harmonics
• High Frequency transient
• Detection and waveform display
• Four current and Four voltage channels

BASIC SPECIFICATIONS

Measurement Lines

Single-phase/two-wires, Single-phase/three-wires, Three-phase/three-wires, Three-phase/four-wires

Measurement Items

Impulsive voltage quality: Transient overvoltage (Impulse)
RMS voltage quality: Voltage swell, Voltage dips, Voltage interruption
Power quality: Frequency, Voltage, Current, Current peak, Active/Reactive apparent power, Power factor (displaced power factor)
Three phase quality: Voltage unbalance ratio, Current unbalance ratio
Harmonic quality (Up to 50th order): Harmonic voltage, Harmonic current, Harmonic power, Inter-harmonic voltage, Inter-harmonic current, Harmonic phase angle, Total harmonic voltage distortion, Total inter-harmonic current distortion (THD-F, THD-R), Total inter-harmonic voltage distortion ratio, Total inter-harmonic current distortion ratio (THD-F, THD-R), K factor
Flicker: Measures delta- V10 flicker (Japanese domestic), or UIE flicker [Pst, Plt] (international standards),

Measurement Ranges

Voltage ch1 to ch3: 150.00 to 600.00 V AC rms-3 ranges
Ch4: 60.000 to 600.00 V AC rms-4 ranges, or 60.000/600.00 V DC-2 ranges
Current (When using 100 A sensor): 50.000/100.00 A AC rms-2 ranges
Current (When using 500 A sensor): 50.000/500.00 A AC rms-2 ranges
Power: Combination pattern of voltage and current ranges

Measurement Method

Transient overvoltage: 2 mega-sampling/sec, Harmonic wave: 2048 point (10 cycle at 50 Hz, or 12 cycle at 60 Hz), Other effective value: 256 point/one cycle

Memory Capacity

13 MB

Interface

PC card slot (flash ATA/528 MB or less), RS-232C, LAN (10BASE-T)

Power Supply

12 V DC output 9458 AC ADAPTER (Universal 100 to 240 V AC, 50/60 Hz), or 9459 BATTERY PACK (7.2 V/2450 m Ah Ni-MH)

Dimensions, mass

298 mm (11.73 in) W × 215 mm (8.46 in) H × 67 mm (2.64 in) D, 2 kg (70.5 oz)...without battery

Accessories

Voltage cord (one set), 9458 AC ADAPTER (1), 9459 BATTERY PACK (1), shoulder strap (1), LAN connector cover (1), marking label (1)

s

 

8205-10 MICRO HiCORDER

True RMS Voltage and Current Recorders with Multimeter Operability!

• Direct current measurement of up to 1000A
• Fast LCD level meter vs. a stylus to quickly
display the measured level
• True RMS rectification system to accurately
read distorted waveforms
• Sampling Rate of 100 samples/second with
selectable chart speeds

BASIC SPECIFICATIONS

Measurement Ranges

DC/AC Voltage: 0.1 V to 500 V f.s. 12 ranges
AC Current: 10 A to 100 A AC 4 ranges (with optional 9650 CLAMP ON SENSOR)
10 A to 500 A AC 6 ranges (with optional 9651 CLAMP ON SENSOR)
10 A to 1000 A AC 7 ranges (with optional 9668 CLAMP ON SENSOR)

Sampling Period

10 ms

Frequency Characteristic

AC/DC voltage range: +0.5 dB to -3 dB from 20 Hz to 30 kHz.
AC current range: Frequency characteristic is determind by the clamp sensor.

Paper Feed Speed

20 cm/minute to 2 cm/hour, 5 ranges

Number of Input Channels

1 channel AC or DC voltage, or 1 channel AC current
(Simultaneous recording not available, one channel may be either type, input is voltage isolated.)

Accuracy

Voltage: ±2 % f.s. (ACV/45 Hz to 66 Hz)
Current: ±3.53 % f.s. (used with 9651 CLAMP ON SENSOR / option, AC 500 A range)

Power Supply

100 to 240 V AC (50/60 Hz) or 9.5 to 14 V DC, 2 way

Dimensions, mass

250 mm(9.4 in)W × 122 mm(4.8 in)H × 93.5 mm(3.66 in)D, 1.2 kg (42.33 oz)

Accessories

9235 Recording paper (1 roll), roll paper holder (2), Power cord (1), 9257 CONNECTION CORD (1), 9344 CARRYING CASE (1)

s

 

8206-10 MICRO HiCORDER

True RMS Voltage and Current Recorders with Multimeter Operability!

• Direct current measurement of up to 1000A
• Fast LCD level meter vs. a stylus to
quickly display the measured level
• True RMS rectification system to accurately
read distorted waveforms
• Climate-resistant recording paper for easy
readability and durability
• Sampling Rate of 100 samples/second with
selectable chart speeds

BASIC SPECIFICATIONS

Measurement Ranges

AC Voltage: 100/200/500 V f.s. 3 ranges
AC Current: 10 A to 100 A AC 4 ranges (with optional 9650 CLAMP ON SENSOR)
10 A to 500 A AC 6 ranges (with optional 9651 CLAMP ON SENSOR)
10 A to 1000 A AC 7 ranges (with optional 9668 CLAMP ON SENSOR)

Sampling Period

10 ms

Frequency Characteristic

AC voltage range: +0.5 dB to -3 dB from 30 Hz to 30 kHz.
AC current range: Frequency characteristic is determind by the clamp sensor.

Paper Feed Speed

60 cm/hour to 2 cm/hour, 5 ranges

Number of Input Channels

1 channel AC voltage and 1 channel AC current
(Simultaneous recording not available, one channel may be either type, input is voltage isolated.)

Accuracy

Voltage: ±2 % f.s. (45 Hz to 66 Hz)
Current: ±3.53 % f.s. (used with 9651 CLAMP ON SENSOR / option, AC 500 A range)

Power Supply

100 to 240 V AC (50/60 Hz) or 9.5 to 14 V DC, 2 way

Dimensions, mass

250 mm (9.4 in) W × 122 mm (4.8 in) H × 93.5 mm (3.66 in) D, 1.2 kg (42.33 oz)

Accessories

9235 Recording paper (1 roll), roll paper holder (2), Power cord (1), 9257 CONNECTION CORD (1), 9344 CARRYING CASE (1)

s

 

3169-20 CLAMP ON POWER HiTESTER

Offering a new approach to energy-related measurement

• Measure up to 3-phase, 3-wire system
(displays voltage and current for three lines)
• Measure up to four single-phase, 2-wire systems
• 5A to 5000A range
• Compact and light weight
• PC card data storage
• Power recording for individual waveforms
• Simultaneous recording of demand values and harmonics

BASIC SPECIFICATIONS

Measurement lines

Single-phase/two-wires, Single-phase/three-wires, Three-phase/three-wires, Three-phase/four-wires

Measurement items

Voltage, Current, Current peak, Active power, Apparent power, Reactive power,
Power factor, Phase angle, Frequency, Power integration, Current integration

Measurement
ranges

Voltage: 150.00 V to 600.00 V, 3 ranges
Current: 5 A to 5 kA, 8 ranges (use clamp sensor)
Shunt input (for current): 50 mV or 100 mV, 2 ranges
Power: 750 W to 9 MW, 16 combination patterns

Basic Accuracy

Voltage: ±0.2 % rdg. ±0.1 % f.s.
Current:±0.2 % rdg. ±0.1 % f.s. + Clamp accuracy (active power, at 45 to 66 Hz)

Clamp sensor accuracy

9660(100 A AC): ±0.5%rdg. ±0.3%f.s.
9661(500 A AC): ±0.5%rdg. ±0.11%f.s.
9669(1000 A AC): ±1.2%rdg. ±0.11% f.s.
9667(5000 A AC, flexible): ±2.2%rdg. ±0.4%f.s.

Frequency
characteristics

Fundamental waveforms up to 50th harmonic ±3 % f.s. + measurement accuracy (of a 45 to 66 Hz fundamental waveform)

Data Storage

Internal memory: 1 MB
Flash Card: Up to 528 MB

Other Functions

RS-232C, External I/O (Option; D/A output)

Display update rate

Approx. 0.5 time/second

Power Supply

100 to 240 V AC, 50/60 Hz

Dimensions, mass

210 mm(8.27 in)W × 160 mm(6.30 in)H × 60 mm(2.36 in)D, 1.2 kg (42.3 oz)

Accessories

9438-03 Voltage cord set, Input cord label, Operation manual, Power cord

 

s 

 

3286-20 CLAMP ON POWER HiTESTER

Functionality and Safety Packed into a Handheld Unit

• Use as a single-phase power meter
• Measure phase on a single-phase line
• Simple checking of three-phase lines
• Check power supply fluctuations
• For harmonic suppression
• External output of data to PC
• Printer output to 9442 (optional)

BASIC SPECIFICATIONS

Measurement lines

Single-phase/two-wires, Three-phase/three-wires (balanced load only)

Measurement items

Voltage, current, voltage/current peak, effective/reactive/apparent power(Single-phase or 3-phase), power factor, reactivity, phase angle, frequency, phase detection(3-phase), voltage/current harmonic levels(up to 20th)

Measurement
ranges

Voltage: 150.0 V to 600 V, 3 ranges
Current: 200.0 A or 1000 A, 2 ranges
Power: 30.00 kW to 1200 kW, 14 combination patterns
Note: 3-phase power is calculated and displayed on the basis of a balanced, 50/60 Hz, sine wave input. For apparent power and reactive power, the unit of watts in the above table is replaced by VA and var respectively.

Basic Accuracy at 50/60 Hz, COS Ø=1

Power/single-phase: ±2.3 % rdg. ±5 dgt., Power/3-phase: ±3.0 % rdg. ±10 dgt. (at balanced load)

Voltage/Current accuracy

Voltage: ±1.0 % rdg. ±3 dgt., Current: ±1.3 % rdg. ±3 dgt. (at 45 to 66 Hz)

Frequency characteristics

30 Hz to 1 kHz

Other Functions

Phase detection, Record (Max. value/Min. value), Battery capacity display, Data hold, Auto power off, Data output (RS-232C interface by optical insulating coupler)

Display update rate


NORMAL: approx. 1 time/ sec
SLOW: 1 time/ 3-sec
HARM meas.: approx. 1 time/ 2-sec

Power Supply

6LR61 alkaline battery × 1
(continuous operation max. 25hours)
6F22 manganese battery × 1
(continuous operation max. 10hours)

Dimensions, mass

62 mm(2.44 in)W × 260 mm(10.24 in)H × 39 mm(1.54 in)D, 550 g (19.4 oz)
Core Jaw Dia..: Ø55 mm(2.17 in), 80mm(3.15in) × 20mm(0.79in) busbar max.

Accessories

9635 VOLTAGE CORD (1), 9245 CARRYING CASE, (1), Hand strap (1)
 

s 

 

3636-20 CLAMP LOGGER

Easy and convenient, clamp-on current recording

• Up to 32,000 measurements data can be collected with the optional 3911-20 for processing by PC
• Effective value rectifier method for correct measurement
• Special software bundled with the 3911-20 enables storing of the recording time, interval, start, end, method and comments in the instrument's memory
• Non-volatile memory preserves collected data even when the battery is depleted

BASIC SPECIFICATIONS

Measurement Lines

AC Current
(with clamp-on sensor, sold separately)

Input Channels

2 channels

Measurement
Ranges

0.00 to 50.00 A, 0.0 to 500.0 A (True RMS)

Accuracy

±2.5 % rdg. ±8 dgt. (at 50/60 Hz, combined accuracy with clamp-on sensor)

Data Memory

16000 data × 2ch
(1-minute interval, total 11 days)
32000 data × 1ch
(1-minute interval, total 22 days)

Recording Interval

1 to 30 seconds, 1 to 60 minutes, 15 settings

Power Supply

4 × 1.5 V, LR03 (AAA) alkaline dry cell batteries, lifetime approx. 1 year
(recording interval 1 minute)

Dimensions, mass

57.5 mm (2.26 in) W × 86.5 mm (3.41 in) H × 30 mm (1.18 in) D, 130 g (4.6 oz)

Accessories

LR03 alkaline dry cell batteries (4), 9632 CONNECTION CABLE (for alarm output, 1)
 

s 

 

3638-20 LEAK LOGGER

Recording and Monitoring Leak Current

• Select from three types of clamp-on leak current sensors
Up to 32,000 measurements data can be collected with the optional 3911-20 for processing by PC
• Effective value rectifier method for leak current measurement
• Special software bundled with the 3911-20 enables storing of the recording time, interval, start, end, method and comments in the instrument's memory
• Non-volatile memory preserves collected data even when the battery is depleted

BASIC SPECIFICATIONS

Measurement items

AC leak current
(w/ clamp-on leak sensor, soldseparately)

Input Channels

2 channels

Measurement
Ranges

100.0 mA, 1000 mA (True RMS)

Combined Accuracy

with 9657 or 9659 sensor: ±2 % rdg.
± 10 dgt. (at 50/60 Hz)
with 9658 sensor: ±4.5 % rdg. ±10 dgt.
(at 50/60 Hz)

Data Memory

16000 data × 2ch
(1-minute interval, total 11 days)
32000 data × 1ch
(1-minute interval, total 22 days)

Recording Interval

1 to 30 seconds, 1 to 60 minutes,
15 settings

Power Supply

4 × 1.5 V, LR03 (AAA) alkaline dry cell batteries, lifetime approx. 1 month (recording interval 1 second)

Dimensions, mass

57.5 mm (2.26 in) W × 86.5 mm (3.41 in) H × 30 mm (1.18 in) D, 130 g (4.6 oz)

Accessories

LR03 alkaline dry cell batteries (4), 9632 CONNECTION CABLE (for alarm output, 1)
 

s 

 

3637-20 AC VOLTAGE LOGGER

Easy and convenient, low-cost voltage recording

• Up to 32,000 measurements data can be collected with the optional 3911-20 for processing by PC
• Effective value rectifier method for correct measurement
• Special software bundled with the 3911-20 enables storing of the recording time, interval, start, end, method and comments in the instrument's memory
• Non-volatile memory preserves collected data even when the battery is depleted

BASIC SPECIFICATIONS

Measurement Items

AC Voltage

Input Channels

1 channel

Measurement
Ranges

0.0 to 600.0 V (True RMS)

Accuracy

±1 % rdg. ±5 dgt. (at 50/60 Hz)

Data Memory

32000 data × 1ch
(1-minute interval, total 22 days)

Recording Interval

1 to 30 seconds, 1 to 60 minutes,
15 settings

Power Supply

4 × 1.5 V, LR03 (AAA) alkaline dry cell batteries, lifetime approx. 1 year (recording interval 1 minute)

Dimensions, mass

57.5 mm (2.26 in) W × 86.5 mm (3.41 in) H × 30 mm (1.18 in) D, 130 g (4.6 oz)

Accessories

LR03 alkaline dry cell batteries (4),
9639 CONNECTION CORD
(for measurement input, 1)
 

 

 